Sceptics like to say a heat pump is useless once it freezes. Ownership statistics disagree: Norway, Sweden and Finland, where January sits far below zero, top the European tables. Cold nevertheless changes the engineering. Capacity shrinks exactly when demand peaks, efficiency slips, ice forms on the outdoor coil, and sizing decisions that are almost irrelevant in mild weather start to decide whether the installation works. The sections below explain what happens under 0 °C and how to plan for a −20 °C spell.
Why the cold costs efficiency
What matters is the temperature lift, the difference between the heat source and the water you send to the radiators. Physics caps the COP at the Carnot limit:
Example: flow 45 °C (318 K), outdoor −15 °C (258 K) COP_max = 318 / 60 ≈ 5.3 → real machine at ~45% of Carnot ≈ 2.4
Two things worsen together. Colder air widens the lift, and a colder day also raises the flow temperature through weather-compensated control, because the house needs more heat. Going from +7 °C outside with 35 °C flow to −15 °C with 50 °C flow roughly doubles the lift and can halve the COP.
Measured performance
Makers publish figures at the EN 14511 rating points. They describe a typical modern cold-climate air-source unit, inverter-driven and using R290, R32 or vapour-injection compressors. Expect a given model to sit within ±15%.
| Outdoor temperature | COP at 35 °C flow | COP at 45 °C flow | COP at 55 °C flow | Capacity vs. rated |
|---|---|---|---|---|
| +7 °C | 4.5–5.3 | 3.6–4.2 | 2.9–3.4 | 100% |
| +2 °C | 3.4–4.0 | 2.9–3.4 | 2.4–2.8 | 85–100% (defrost) |
| −7 °C | 2.8–3.4 | 2.4–2.9 | 2.0–2.4 | 75–100% |
| −15 °C | 2.2–2.7 | 1.9–2.3 | 1.6–2.0 | 65–90% |
| −25 °C | 1.6–2.0 | 1.4–1.8 | 1.2–1.5 (if supported) | 50–75% |
A 2023 Joule review by Gibb, Rosenow and colleagues combined field and laboratory results. Air-source heat pumps kept COPs near 2 at −10 to −15 °C, and in most tests stayed above 1.5 at −20 °C or colder. Even at the worst moment, then, a heat pump beats resistance heating, and those moments are rare.
Why the seasonal figure stays healthy
Severe cold is infrequent. Across a heating season, Oslo, Helsinki and Montréal spend most hours between −5 °C and +8 °C. A unit that manages only COP 1.8 at −20 °C might be there for just 50–150 hours a year. The seasonal performance factor (SPF) weights each temperature by the heat actually delivered, so a cold location usually ends up 0.3–0.7 points below a mild one instead of collapsing.
Typical SPF for a 45 °C system, air-source versus ground-source:
- Mild (London, Paris, Seattle): 3.0–3.6 air, 3.8–4.5 ground.
- Cold (Berlin, Warsaw, Bucharest, Chicago): 2.7–3.3 air, 3.6–4.3 ground.
- Very cold (Oslo, Helsinki, Montréal, Harbin): 2.4–3.0 air, 3.4–4.1 ground.
- Subarctic (Fairbanks, northern Lapland): 1.8–2.5 air, 3.0–3.8 ground.
Defrosting
Humid air below 0 °C deposits frost on the outdoor coil and chokes airflow, so the machine reverses for 2–10 minutes and melts the ice using heat from the house. Counter-intuitively, −20 °C is not the worst case, since that air is dry. Frost peaks near −3 °C to +3 °C when humidity is high, conditions that are routine in maritime and continental winters. There, defrosting consumes about 2–10% of delivered energy. Ways to reduce it:
- Lift it onto a stand or wall bracket, 30–50 cm above where snow will lie.
- Fit a drain that will not freeze, because ice growing under the unit is a typical failure.
- Stay clear of drifts and dripping roof edges; a little canopy can help.
- Prefer sensor-driven, demand-based defrost over timed cycles.
Sizing against the design temperature
The design outdoor temperature is the cold-day figure a system has to cope with, and it is beaten on only a handful of days a year. Berlin uses about −12 °C, Bucharest −14 °C to −16 °C, Oslo −20 °C, Helsinki −26 °C, and Montréal or Minneapolis roughly −23 °C to −30 °C. For an exact value, check national standards or ASHRAE climate data.
You can size in two ways.
- Monovalent: one heat pump meets the full design load alone. It is straightforward, though for most of the season the machine is bigger than needed.
- Bivalent: the heat pump carries the load down to a bivalent point, commonly −5 °C to −10 °C, and below that an electric element or the old boiler adds the shortfall.
Since the coldest hours are so scarce, a unit sized for 80–90% of peak load usually still provides 95–99% of annual heat, and the resistance heater’s small remainder adds little cost.
Example: a 160 m² house near Oslo
- Design heat loss is 9 kW at −20 °C (a renovated 1990s house), with annual heat demand of 21,000 kWh.
- Option A: a 9 kW cold-climate air-to-water unit supplies ~70% (6.3 kW) at −20 °C, with a 6 kW backup element stepping in below about −12 °C. An hourly simulation shows backup ≈ 3% of heat and SPF ≈ 2.8, so the house needs 21,000 / 2.8 ≈ 7,500 kWh of electricity.
- Option B: a ground-source system with 120 m of borehole (two 60 m wells in typical Norwegian bedrock) reaches SPF ≈ 3.8 and uses ≈ 5,530 kWh.
- B uses
2,000 kWh less, worth about €260 a year at NOK 1.5/kWh (€0.13), yet it costs €10,000–15,000 extra. Such a long payback explains why air-source still leads in new Norwegian homes. - Compared with direct electric heating, either choice saves 5,000–20,000 kWh.
To test other climates, open the heat pump calculator; borehole sizing lives in the ground source heat pump calculator.
Air-to-air units
Most heat pumps in Scandinavia and Japan are not hydronic. They are simple air-to-air splits on a living-room wall. Nordic-market models quote a SCOP of 4.5–5.5 in the EU “colder” reference climate, and keep working down to −25 °C or −30 °C. Where a home relies on resistance heaters, one €2,000–3,500 unit in the open-plan area can cut heating electricity by 30–50%. You get no hot water, though, and closed bedrooms stay cool.
Other heat sources
From about 2 m down, ground temperature matches the yearly average air temperature: roughly +5 to +8 °C in Scandinavia, +9 to +12 °C in central Europe. Even in February a borehole collector returns brine at about 0–5 °C, so the lift stays almost constant and defrost never happens. The catches are cost and long-term sizing: drilling runs €40–80 per metre in Europe, and the boreholes need enough length to avoid depleting ground heat over decades.
Alternatives:
- Hybrids couple an air-source unit with a gas or oil boiler already in place to cover the coldest hours, which works where the grid is constrained or radiators cannot be upgraded.
- CO₂ (R744) units efficiently make 65–90 °C water, a good match for hot water in cold regions.
- Exhaust-air units extract heat from the ventilation air of airtight Nordic houses.
What cold snaps do to the grid
At scale, the coldest hours decide peak electricity demand. A heat pump at COP 2 needs half the electricity of a resistance heater to give the same heat, so replacing direct electric heating (common in Norway, Sweden, France and Quebec) lowers winter peaks, whereas replacing gas pushes them up. Houses that are well insulated and hold plenty of heat can switch heating off for a peak hour, and smart tariffs are starting to pay for this. Grid mixes by country are on the world energy map.
Before you install
Start with a real heat-loss calculation at your local design temperature instead of copying the old boiler’s rating, and insulate first, since every kW of loss you remove shrinks both the equipment and the electricity bill (try the insulation savings calculator). Then shop for a unit whose capacity and COP are published at −15 °C and −20 °C; North American buyers can filter by the NEEP cold-climate list. Keep the flow temperature as low as the radiators permit, 35–45 °C at design conditions.
At the house, stand the outdoor unit above the snow and shelter it from the wind, adding a heated or frost-protected drain. Let the backup heater run only below the bivalent point and keep an eye on its consumption. Last, add up total costs, counting gas standing charges you can cancel, in the heating cost comparison.
Summary
Capacity and efficiency do fall with the thermometer. Even so, at −15 °C today’s cold-climate units still give roughly two units of heat per unit of electricity, and good Nordic systems reach seasonal performance well above 2.5. Design decides the result: size for the real design temperature, keep flow temperatures low, site the outdoor unit well and treat the backup heater as only a backup. Start with Heat Pumps Explained if COP and running costs are new to you.
Calculators related to this topic
Frequently asked questions
How cold can it get before a heat pump gives up?
What COP can I expect at −15 °C?
Is a backup heater necessary where winters are cold?
Does ground-source beat air-source in the cold?
Why does steam come off my outdoor heat pump in winter?
Where are heat pumps common in cold regions?
Sources & references
- IEA (2022). The Future of Heat Pumps
- Gibb, D., Rosenow, J., Lowes, R., Hewitt, N. (2023). Coming in from the cold: Heat pump efficiency at low temperatures. Joule 7(9)
- NREL — Cold Climate Air Source Heat Pump field and laboratory studies
- Northeast Energy Efficiency Partnerships (NEEP) — Cold Climate Air Source Heat Pump Specification and product list
- European Heat Pump Association (EHPA) — Market and statistics reports
The figures in this guide are typical ranges taken from the listed sources, and your own values will vary with location, prices and equipment. For estimates specific to your site, use the linked calculators.