Pumped hydro storage
A storage method that pumps water uphill to a reservoir when electricity is cheap or plentiful and sends it back through turbines when demand rises; worldwide, it is the biggest type of grid storage.
Most grid storage energy capacity installed worldwide is pumped storage hydropower (PSH). Power capacity stands at about 180–190 GW (IHA 2024), and the stored energy is on the order of 9,000 GWh, although batteries are now adding power capacity faster. The largest fleets belong to China, Japan and the United States.
How much energy a plant stores depends on the volume of water and the head:
A million m³ at 400 m head holds about 1,090 MWh before losses. Main characteristics:
- Round-trip efficiency: 70–85% for modern plants
- Duration: usually 6–20 hours at full output, and far longer in some seasonal schemes
- Response: 1–3 minutes to start generating from rest, seconds when already spinning. Variable-speed and ternary units can also regulate power during pumping.
- Service life: 50–100 years for the civil works, with electromechanical overhauls every 30–40 years
Reversible Francis pump-turbines equip most plants. Large examples are Fengning (China, 3.6 GW), Bath County (US, about 3 GW) and Dinorwig (UK, 1.7 GW, which is known for its black-start capability).
Sites need the right terrain, building takes 5–10 years, and the up-front capital is steep. Closed-loop "off-river" schemes, which ANU has mapped globally, spare rivers from impact and are drawing interest as long-duration storage for grids dominated by renewables.
Related terms
All terms →- Hydraulic head
Vertical distance from the water level at a hydropower intake down to the turbine outlet (tailwater); multiplied with flow, it fixes the power on offer.
- Francis turbine
A reaction hydro turbine with fixed blades, where water flows in radially and out axially; the most installed design, suited to medium heads of about 30 to 700 m.
- Round-trip efficiency
The portion of the energy fed into a storage system that comes back out on discharge, measured at a stated boundary (cell, DC side or AC grid connection).
- Long-duration energy storage (LDES)
Storage that can discharge at full rated power for about 8 hours or longer, bridging multi-day lulls and seasonal gaps that 2–4 hour batteries cannot cover.
- Black start
Rebuilding a power system after a full or partial blackout, beginning with units able to start without any power from the grid.
- LCOS (Levelized Cost of Storage)
Lifetime average cost for each MWh a storage asset discharges, covering investment, operation, charging electricity and efficiency losses.