Hydropower is old, big and flexible. About 4,400 TWh came from it in 2025, some 14% of world electricity: more than nuclear, wind or solar individually. The International Hydropower Association counts roughly 1,400 GW installed, pumped storage included. Wind and solar cannot do what it does alone, which is store energy in bulk for long periods and follow demand within minutes. Norway, Brazil and Canada rest their grids on it, and elsewhere it is a growing asset beside variable renewables.
Principle
Elevated water holds potential energy. It runs down a penstock, gains pressure, and spins a turbine runner. A synchronous generator on the shaft delivers alternating current at grid frequency; a transformer lifts the voltage.
Output depends on two things only: flow, and hydraulic head, the vertical drop.
ρ = density of water (≈ 1,000 kg/m³) g = gravitational acceleration (9.81 m/s²) Q = flow rate through the turbine (m³/s) H = net head after friction losses in the penstock (m) η = overall efficiency of turbine, generator and transformer (≈ 0.85–0.93)
Example: Q = 100 m³/s, H = 80 m, η = 0.90 → P ≈ 1,000 × 9.81 × 100 × 80 × 0.90 ≈ 70.6 MW
Flow and head carry equal weight. A small mountain stream dropping 600 m can match a broad lowland river dropping 6 m, though the machines differ completely. Test the formula on a stream with the micro-hydro calculator.
Turbine families
- Francis: reaction type; water enters radially through guide vanes and leaves axially. Heads from about 10 m to 700 m make it the standard for big dams, including the 700 MW units of Three Gorges and Itaipu. Efficiency peaks above 94%.
- Kaplan: adjustable-blade propeller for heads of about 2–40 m and large flows, common in run-of-river plants. The bulb turbine, a Kaplan variant with its generator sealed inside the water passage, handles very low heads and tidal barrages.
- Pelton: impulse type. Jets from nozzles hit spoon-shaped buckets. Suited to about 200 m up to over 1,800 m of head at modest flow: alpine and Norwegian schemes.
- Crossflow and Turgo: small hydro, where low price and toughness beat peak efficiency.
Three plant concepts
Reservoir
A dam turns a valley into a store holding days, seasons or years of inflow. Operators release water when power sells best, making the plant a rain-charged battery. Irrigation, flood protection and drinking water share the lake and sometimes clash with generation. The giants are all of this type:
- Three Gorges, China: 22.5 GW, typically about 100 TWh a year
- Baihetan, China: 16 GW
- Itaipu, Brazil–Paraguay: 14 GW, annual records above 100 TWh
- Xiluodu, China: 13.9 GW
- Belo Monte, Brazil: 11.2 GW
- Guri, Venezuela: about 10 GW
Run-of-river
Part of the river is diverted through a channel or tunnel, or held by a low weir with a few hours of pondage at most. Production follows the river and peaks with snowmelt or the wet season. Little flooding and resettlement; fish passage and minimum flows remain issues. Large stretches of the Danube, Rhine and Columbia are used mostly this way.
Pumped storage
Water is lifted to an upper reservoir when electricity is cheap or abundant and dropped when it is short. Reversible pump-turbines deliver about 70–85% round trip. IHA (2024) counts roughly 180–190 GW installed, still over 90% of the world’s stored electricity by energy; China builds the most. The record holder is Fengning in Hebei at 3.6 GW. Off-river “closed-loop” designs avoid rivers entirely; the Australian National University has catalogued hundreds of thousands of candidate sites around the world. A scheme can be sized in the pumped hydro storage calculator, and battery storage is the main alternative.
Small, mini, micro
Small usually means under 10 MW (30 or 50 MW in some countries), mini under 1 MW, micro under 100 kW. Villages in Nepal, Peru and East Africa run on micro hydro, often the cheapest off-grid supply wherever a reliable stream has some fall.
Performance
Water-to-wire efficiency reaches 90–95% in well-kept large plants, versus 35–60% for thermal stations and about 20–23% for solar modules. Capacity factor tells another story, being capped by water supply and by running for peaks.
| Parameter | Reservoir | Run-of-river | Pumped storage |
|---|---|---|---|
| Typical head | 30–300+ m | 2–50 m (diversion schemes higher) | 100–800 m |
| Main turbine type | Francis, Pelton | Kaplan, bulb, Francis | Reversible Francis pump-turbine |
| Water-to-wire efficiency | 85–93% | 85–92% | 70–85% round trip |
| Capacity factor | 30–60% | 40–70% (seasonal) | 10–25% (depends on market) |
| Response time | seconds to minutes | limited by flow | seconds to minutes |
| Lifetime | 50–100+ years (civil works) | 40–80 years | 50–100 years |
IRENA data show new hydro averaging about 45–55% capacity factor globally in recent years, with wide scatter. Peaking plants in Norway and Switzerland deliberately run fewer hours; steady equatorial rivers run more. Rain makes output vary year to year, as drought showed in Europe (2022), China’s Sichuan and Yunnan (2022–2023) and Brazil (2021).
Costs
Capital cost is high and site-specific, running costs low. IRENA’s Renewable Power Generation Costs in 2023 (2024): global weighted-average LCOE about USD 0.057/kWh for plants commissioned in 2023, at installed costs near USD 2,800/kW, higher than earlier this decade because sites are more remote and complex. Individual projects diverge widely. Large plants in China, Brazil and Africa come in below USD 0.03/kWh; hard small or remote sites exceed USD 0.15/kWh by a good margin. Lazard’s LCOE+ says little about new hydro. In NREL’s ATB, new US hydro on undeveloped reaches ranks among the dearer renewables, since the best sites were dammed long ago. Retrofitting existing dams, or powering unpowered ones, is often far cheaper.
Two caveats for LCOE comparisons. Dams and tunnels can last a century. A plant depreciated over 30–40 years therefore goes on producing at very low marginal cost, and most hydro in Europe and North America dates from before 1980. Overruns are also common: Ansar et al. (2014), looking at 245 large dams, found real-terms cost overruns of about 96% and schedule delays of 44% on average. Pumped storage is better compared by LCOS, usually against batteries at eight hours or more.
Footprint
Flooded land per unit of energy spans orders of magnitude: well under 1 m² per MWh/yr at high alpine schemes, tens of square metres at shallow lowland reservoirs such as Brazil’s Balbina, which put about 2,400 km² under water for 250 MW. Three Gorges submerged about 630 km² and moved about 1.3 million people. The World Commission on Dams (2000) counted 40–80 million people uprooted by dams worldwide, a large share without fair compensation.
Hydro does not use water for cooling, yet reservoirs evaporate it, which in hot dry climates can be large per MWh. Dams cut rivers into segments, trap sediment that would feed downstream deltas and farmland, and change temperature and oxygen levels. Concrete, rock fill and steel dominate materials; spread over a very long life, that is little per MWh.
Life-cycle CO2
No other renewable spans such a range. IPCC AR5 WGIII Annex III (2014): median near 24 gCO2e/kWh, range about 1 to 2,200 gCO2e/kWh. Alpine and Nordic high-head plants are at the bottom. The very highest values belong to a few shallow tropical reservoirs. There, submerged vegetation and organic inflow decompose without oxygen and methane escapes from the surface, through turbines and spillways (“degassing”), and further downstream. For typical plants, leaving out the extreme reservoirs, UNECE (2021) reports roughly 6 to 150 gCO2e/kWh.
Over 20 years methane warms about 80 times more than CO2, and it is what pushes the worst cases so high. They peak during the first decade after flooding and vary with climate, depth, area per MW and organic load. The IHA and UNESCO G-res tool estimates net reservoir emissions before construction. Temperate and boreal hydro, and run-of-river in general, land near wind and nuclear.
Safety and wider impacts
Dam failure. Per TWh few die, but the tail is heavy. Extreme rain from Typhoon Nina in 1975 broke the Banqiao and Shimantan dams in Henan, China, and then dozens more downstream; estimates run from about 26,000 to over 170,000 deaths including famine and disease. Others: In Italy, Vajont (1963) killed about 2,000 when a landslide sent a wave over the dam; in India, Machchu-II failed in 1979. Modern design, spillways for extreme floods, monitoring and emergency planning have made disasters uncommon. Ageing dams and heavier rainfall in a warming climate are the growing concern.
Ecology. Salmon, sturgeon and eels cannot pass dams. Fish ladders, bypass channels and fish-friendly turbines lessen but seldom eliminate the harm. Altered flows reach wetlands and floodplains, and “hydropeaking”, the abrupt changes in discharge that follow demand, hurts life downstream. Dam removals in Europe and the US, such as Washington’s Elwha River, show how quickly fish can return.
People. Big hydro stays political because of displacement, loss of farmland and heritage, and quarrels over shared rivers: the Nile and the Grand Ethiopian Renaissance Dam, the Mekong, the Indus. Criteria for consultation, compensation and environmental flows are set out in the IHA’s Hydropower Sustainability Standard.
Countries that run on hydro
- Norway: close to 90% of electricity; huge reservoirs balance Nordic and continental markets via interconnectors.
- Brazil: historically around 60%, from Itaipu, Belo Monte and the Tucuruí complex.
- Canada: roughly 60%, led by Quebec, British Columbia and Manitoba, with large exports to the United States.
- Paraguay, Ethiopia, Nepal, Democratic Republic of Congo: above 90%.
Find individual plants on the power plants map.
Outlook
In its Hydropower Special Market Report (2021) the IEA described hydro as clean power’s “forgotten giant”, predicting slower growth beyond China once the best sites are taken and opposition stiffens. Most new conventional capacity is being built in China, India, Africa and South-East Asia. Pumped storage is expanding faster, driven by wind and solar balancing needs; China alone has well over 100 GW either being built or approved. Gains with little extra impact are available: old fleets in Europe and North America can be refurbished and uprated, existing dams fitted with generators, reservoirs covered with floating solar, and hydro paired with solar in hybrid operation. The climate effect is mixed: some high-latitude basins gain water, while the Mediterranean, southern Africa and parts of South America lose it. Compare with other sources on the technology comparison page; marine energy is hydro’s ocean cousin.
Frequently asked questions
How does a hydro dam make electricity?
What fraction of the world's electricity is hydro?
Can hydropower be called carbon neutral?
How do run-of-river and reservoir plants differ?
Which hydroelectric dam is the largest?
What round-trip efficiency does pumped hydro have?
What happened at Banqiao?
Sources & references
- IRENA (2024). Renewable Power Generation Costs in 2023
- IEA (2021). Hydropower Special Market Report
- International Hydropower Association (2024). World Hydropower Outlook
- IPCC (2014). AR5 WGIII Annex III: Technology-specific Cost and Performance Parameters
- UNECE (2021). Life Cycle Assessment of Electricity Generation Options
- NREL. Annual Technology Baseline (ATB) — Hydropower and Pumped Storage Hydropower
- Electricity statistics by Ember and the Energy Institute, supplied through Our World in Data and used for this page's charts and tables